Per unit value=  actual value of a quantity/base value of a quantityPer\ unit\ value=\ \ actual\ value\ of\ a\ quantity/base\ value\ of\ a\ quantity

Key Formulas

There are two primary formulas used when performing per-unit network calculations:

1. Transformers and Generators
These components typically have a per-unit impedance value provided by the manufacturer, based on their design characteristics. When converting this impedance to a different base for system calculations, the following formula is applied:

Zpu new=Zpu given×Sbase/SratedZ_{pu \ new }=Z_{pu \ given}\times S_{base} /S_{rated}

2. Overhead Lines and Underground Cables
For these assets, impedance is usually specified in ohms. To express this impedance in per-unit terms on the chosen base, use:

Zpu=ZΩ×Sbase /((Vbase  )2 )Z_{pu}=Z_\Omega\times S_{base}\ /((V_{base}\ \ )^2\ )

Here, represents the operating voltage of the asset.

Per-Unit Analysis – Solution Steps

Solving a per-unit network problem typically involves the following steps:

  1. Select Base Values
    Begin by choosing a common base for apparent power () and voltage (). These values will serve as the reference for converting all system quantities into per-unit form.
  2. Convert Asset Impedances to Per-Unit
    Transform the impedance values of all components—such as transformers, lines, and loads—into their per-unit equivalents using the chosen base values. This ensures consistency across the entire network.
  3. Simplify the Network
    Replace all actual impedances with their per-unit equivalents and reduce the circuit to a simpler form. This may involve combining series or parallel impedances to create an equivalent representation.
  4. Perform the Required Calculation
    Once the network is simplified, carry out the desired analysis—such as calculating voltage drops, determining sending-end voltage, or performing fault studies.

We will now apply these steps to determine the sending-end voltage for the transformer in the following network:

Step 1 – Select a Common Base Power ()

Begin by choosing a single base power for the entire circuit. For this example, we will use 100 MVA as the base, as this is the typical value used within industry. However, any convenient value can be selected, provided it remains consistent throughout the analysis.

Step 2 – Convert Each Asset to the Common Base Impedance

  • Transformer 1 (22/400 kV): Rated at 200 MVA with an impedance of 0.1 pu on its own base. To convert this to the 100 MVA base:
Zpu new=Zpu old×Sbase /Srated  =0.1×100/200=0.05puZ_{pu\ new} =Z_{pu \ old}\times S_{base}\ /S_{rated}\ \ =0.1\times100/200=0.05pu
  • Transformer 2: Already rated at 100 MVA, so its impedance remains unchanged at 0.08 pu.
  • Overhead Line (OHL1): For the overhead line, the impedance is given in ohms. Convert it to per-unit using:
ZOHL1=ZΩ×Sbase /(Vbase  )2 =(j4.0×(100×106))/(400×103 )2 =j0.0025 puZ_{OHL1}=Z_\Omega\times S_{base}\ /(V_{base}\ \ )^2\ =(j4.0\times(100\times10^6))/(400\times10^3\ )^2\ =j0.0025\ pu

Step 3 – Reduce the circuit to allow a simple resolution

The common per unit values for each asset, can be used to simplify the network below:

Total Impedances can be calculated as follows:

ZT=0.05+0.0025+0.08=j0.1325puZ_T=0.05+0.0025+0.08=j0.1325pu

Step 4 – Performing required operation – calculating VS

The specified load values introduce a challenge. The problem defines the load in terms of real power  (in watts) rather than apparent power  (in volt-amperes), which is typically required for system calculations. Furthermore, the line current  is not provided, preventing calculation of the voltage, .

Calculating apparent power of the load SL :

SL=PLcos=VIS_L=\frac{P_L}{\cos{\emptyset}}=VI
SL=500.80=62.5MVA\therefore S_L=\frac{50}{0.80}=62.5MVA

Calculating the current I:

We do not have a value for I, we can use the power values of the load as a ratio with the base power (SB) to give a per unit value of current, as the current is determined by load.

IL pu=SLSB=62.5100=0.625 puI_{L\ pu}=\frac{S_L}{S_B}=\frac{62.5}{100}=0.625\ pu

Calculating the current I:

IL pu gives a value of 0.625, this is the magnitude of the current. The angle is given by

Cos1(0.8)=36.9°Lagging=36.9°{Cos}^{-1}\left(0.8\right)=36.9° Lagging= -36.9°
In rectangular formthisgivesILpuas0.4998  j0.3753 pu.In \ rectangular\ form \\ this \\ gives\\ I_L\\ pu \\ as \\ 0.4998\ -\ j0.3753\ pu.

Calculating the sending end voltage VS:

VS=VR+(IL pu×ZT)=(1+j0)+((0.4998j0.3753)×(0+j0.1325))=1.0497+j0.066puV_S=V_R+\left(I_{L\ pu}\times Z_T\right)=\left(1+j0\right)+\left(\left(0.4998-j0.3753\right)\times\left(0+j0.1325\right)\right)=1.0497+j0.066pu
|VS|=1.04972+0.0662=1.0518 pu\left|V_S\right|=\sqrt{{1.0497}^2+{0.066}^2}=1.0518\ pu

Converting from the per-unit to the actual value:

VS=1.0518×132k=138.8kVV_S=1.0518\times132k=138.8kV

Calculation of a power system in a balanced fault scenario

Step 4 – Performing required operation – balanced fault calculations MVAS/C & IS/C

A 3-phase balanced fault occurs just before our 50 MW load.

To calculate the balanced fault apparent power (MVAS/C) we need to know the magnitude of the total impedance to the point of fault.

Calculating the magnitude of total impedance │ZT│:

|ZT|=(02+j0.1325pu2)=0.1325 pu \left|Z_T\right|=\sqrt{\left(0^2+{j0.1325pu}^2\right)}=0.1325\ pu\
(Note:There is no resistance, so the magnitude is just the imaginary part only)(Note:There\ is\ no\ resistance,\ so\ the\ magnitude\ is \ just\ the\ imaginary\ part\ only)

Calculating the balanced fault power:

MVAS/C=SB|ZT|=1000.1325=754.7 MVA{MVA}_{S/C}=\frac{S_B}{\left|Z_T\right|}=\frac{100}{0.1325}=754.7\ MVA

To determine the balanced short-circuit fault current (), it is necessary to know the fault apparent power () and the system voltage at the fault location. These parameters allow calculation of the current magnitude under balanced fault conditions.

Calculating the short circuit fault current IS/C:

𝐈S/C=MVAS/C3×V=754.7×1063×132×103=𝟑.𝟑𝐤𝐀\mathbf{I}_{S/C}=\frac{{MVA}_{S/C}}{\sqrt3\times V}=\frac{754.7\times{10}^6}{\sqrt3\times132\times{10}^3}=\mathbf{3}.\mathbf{3kA}